Dusk to dawn IP66 Photocell LT124L 105-305V for Street lights and shoebox light fixtures Day Night Sensor

Our street lighting photocells are ANSI C136.10 compliant, providing a cost-effective and dependable solution for automated lighting control from dusk to dawn. Engineered to optimize lighting system performance and save energy, these photocells utilize advanced electronic circuitry and a stable phototransistor light sensor for consistent on/off functionalit

Product information
Model:LT124L
Standard:ANSI C136.10 & UL773
Rated Volts:120V-277V (Applicable: 105-305V)
Rated Load:1000W/1800VA
LED Rating:2A E-Ballast
Turn-On Light Levels:10-16 Lux

ON/OFF Ratio:1:1.5
Time Delay:3-10 Seconds
Switch:>5000 ON/OFF Operations at Rated Load
Power Consumption:≤ 0.5 watts at 120VAC
Cover:Anti-UV Impact Resistance Polypropylene
Base:High Temperature Resistance Polybutylene Terephthalate
Fail Mode:ON or OFF

Dusk to dawn IP66 Photocell LT124L 105-305V for Street lights and shoebox light fixtures Day Night Sensor

Why the LT124L

One photocell platform that adapts to the project instead of forcing the project to adapt to it: an IR phototransistor that holds its threshold for years, MOV surge protection you size from 320J to 1,280J, delay and fail-mode options for the site’s real conditions, IP66/67 sealing, and a part number that records every choice. ANSI C136.10 compliant, UL773 listed design, −40°C to +70°C, 3-year one-for-one warranty — specified once, documented forever.

Built for the Field, Documented for the Submittal

  • Reliable sealed relay on an FR4 fibreglass PCB — the switching element is sealed against dust and moisture.
  • Operates down to 90V AC on a 105–305V supply window — headroom for long runs and voltage sag.
  • Fail mode as a choice: fail-off standard, fail-on where the application requires lighting to stay up if the control fails.
  • IP66 standard, IP67 optional — jet-water tight, with immersion protection where wash-down or flooding is expected.
  • UL94 V-0 flame-resistant housing (anti-UV impact polypropylene, 2.00mm) over a high-temperature PBT base.
  • Drop-tested: 1m onto concrete without housing damage or change of electrical operation.
  • RoHS compliant, ISO-manufactured, UL773 / ANSI C136.10 — with month/year of manufacture and serial number marked on every unit.

Follow these four steps to install the Twist-lock photocell:

  1. Align the larger pin with the larger hole and insert it
  2. Push downward
  3. Twist clockwise to lock

The twist-lock design only holds firm after the clockwise rotation. Skipping that last turn leaves the photocell sitting in the socket without being mechanically locked — which is why it may feel unstable or pull out easily.

twist- lock photocellI installation-Diagrams

Key Specifications

ItemSpecification
ModelLT124L twist-lock electronic photocontrol
StandardsANSI C136.10, UL 773
Rated voltage120–277V AC (applicable 105–305V), 50/60 Hz
Rated load1000W / 1800VA
LED rating2A E-Ballast
Turn-on / off16 ± 6 lux on; off at 1.5 × turn-on level
Time delayInstant ON; 3–6s OFF delay (longer options available)
Light sensorIR-filter phototransistor (sealed; CDS not used)
Surge protection6kV; MOV from 320J (options to 1,280J)
Insulation resistance>500 MΩ
Ingress protectionIP66 standard; IP67 optional
Operating temperature−40°C to +70°C
Power consumption≤0.5W at 120V AC
HousingAnti-UV impact polypropylene cover (2.00mm), UL94 V-0; PBT base
Switching life>5,000 operations at rated load
Warranty3 years (one-for-one replacement)

Applications

  • LED luminaires requiring dusk-to-dawn control
  • Solid-state ballast / driver loads: CFL, induction, electronic HID
  • LED, HID, induction, fluorescent and halogen systems
  • Roadways and street lighting
  • Parking lots and security lighting

FAQ

Q1. What is the difference between the LT124L and a fixed-configuration photocell? Every field-relevant parameter — turn-on level, time delay, fail mode, MOV joules, IP rating and cover colour — is a selectable option ordered through the part-number code, so the product matches the site rather than the reverse.

Q2. Why is an IR phototransistor better than a CDS cell? CDS cells drift with temperature and ageing, shifting the switching threshold over time. The LT124L’s sealed IR-filter phototransistor holds its 16 ± 6 lux window stable across seasons and the full service life.

Q3. How much surge protection does the LT124L have? The standard configuration carries a 320J MOV with 6kV surge protection; 640J, 960J and 1,280J MOV options are available for higher-exposure sites.

Q4. What does “Fail-Off” and “Fail-On” mean? It is the state the lighting takes if the control fails. Fail-Off (standard) is the economical default; Fail-On is specified where lighting must remain up after a control failure — for example security and safety lighting.

Q5. Can the LT124L run LED fixtures? Yes — the 2A electronic-ballast rating is designed for LED drivers and other solid-state loads (CFL, induction, electronic HID), alongside incandescent and ballasted loads up to 1000W/1800VA.

Q6. What documentation comes with an order? Each unit is marked with month/year of manufacture, serial number, model description, voltage range and load rating; datasheets and test documentation are provided with the quotation.

Build your part number, send it over. Choose the cover colour, turn-on level, delay, fail mode, MOV rating and IP grade from the table above — or tell us the site conditions and we will specify the configuration for you. Quotations, datasheets and samples are returned within 48 hours.

[Request a Quote for LT124L] · [Get a Sample] · info@leaditop.com

Get A Free Consultation
And Estimate

Join our Mailing list!

Stay Informed with Exclusive Updates.

“To receive light control market trends, industry news, and new product releases.”